产品简介
Switchgear
The switchgear producted by CEMSA, main products include MNS, GCS, GCK, GGD, KYN28a, KYN and other high and low voltage distribution cabinet cabinets and complete equipment.
- 规格系列:GCS low voltage draw out complete switchgear
XGN2-12 box fixed AC metal enclosed switchgear
GCK low voltage draw out switchgear
服务电话+86 13521339794
获取价格
在线留言
enfi.cemsa@gmail.com
优势特点
工作原理
GCK low voltage draw out switch cabinet: applicable to power plants, substations, industrial and mining enterprises and other power users as the power system with AC 50Hz, maximum working voltage up to 660V and maximum working current up to 4000A. It is used for power distribution, motor control and other power distribution equipment for power conversion and distribution control.
GCS low voltage draw out switchgear: suitable for power distribution system in power plant, petroleum, metallurgy, textile, chemical industry, high-rise building and other industries. In large power plants, petrochemical systems and other places with high degree of automation and requiring computer interface, it is used as a complete set of low-voltage power distribution devices for power generation and supply systems with three-phase AC frequency of 50Hz, rated working voltage of 400V and rated current of 4000A and below, power distribution in motor system, centralized control of electric machines and reactive power compensation.
Xgn2-12 box type: it is suitable for receiving and distributing electric energy in the power system with rated voltage of 3.6 ~ 12kV, three-phase AC 50Hz and rated circuit of 630 ~ 4000A. It is especially suitable for frequent operation.
GCS low voltage draw out switchgear: suitable for power distribution system in power plant, petroleum, metallurgy, textile, chemical industry, high-rise building and other industries. In large power plants, petrochemical systems and other places with high degree of automation and requiring computer interface, it is used as a complete set of low-voltage power distribution devices for power generation and supply systems with three-phase AC frequency of 50Hz, rated working voltage of 400V and rated current of 4000A and below, power distribution in motor system, centralized control of electric machines and reactive power compensation.
Xgn2-12 box type: it is suitable for receiving and distributing electric energy in the power system with rated voltage of 3.6 ~ 12kV, three-phase AC 50Hz and rated circuit of 630 ~ 4000A. It is especially suitable for frequent operation.
技术参数
GCS | Technical parametersⅠ | GCK | Technical parametersⅡ | XGN2 | Technical parametersⅢ |
---|---|---|---|---|---|
Rated voltage of main circuit (V) |
Communication 380 (400),660 | Rated insulation voltage (V) | 660 | Project | |
Rated voltage of auxiliary circuit (V) |
AC 220, 380 (400) DC 110,220 | Rated working voltage of main circuit (V) |
380 | Rated voltage(kV) | 3;6;10 |
Rated frequency (Hz) | 50(60) | Rated working voltage of auxiliary circuit (V) |
AC380.220;DC220.110 | Maximum operating voltage(kV) | 3.6;7.6;12 |
Rated insulation voltage (V) | 660(1000) | Rated frequency (Hz) | 50 | Rated current(A) | 5~2500 |
Rated current (a) Horizontal bus |
≤4000 | Rated working current (a) | 630、1000,1600、 2000.2500.3000 |
Rated short-circuit breaking current(kV) |
16;20;31.5;40 |
Rated current (a) Vertical bus (MCC) |
1000 | Rated short-time withstand current (KA) |
50/30.30 (neutral bus) | Rated short circuit closing current(kV) |
40;50;80;100 |
Rated short-time withstand current of bus (ka/1s) |
50、80 | Rated peak withstand current (KA) |
63.105 | Rated dynamic stable current(kV) |
40;50;80;100 |
Rated peak withstand current of bus (Ka/0.1s) |
105、176 | Functional unit (drawer) breaking capacity (KA) 50 (effective value) |
Functional unit (drawer) breaking capacity (KA) 50 (effective value) |
Rated thermal stability current(kV) |
16;20;31.5;40 |
Power frequency test voltage (V/1min) Main circuit |
2500 | Motor capacity range (kw) | 0.45- 160 | Rated thermal stability time(s) |
4 |
Power frequency test voltage (V/1min) Auxiliary circuit |
2360 | Dielectric strength (v/1min) | 2500 | Protection level | IP2X |
A bus or bus bar Three phase four wire system |
A、B、C、NPE | Enclosure protection level | IP30 | Bus system | Single bus |
A bus or bus bar Three phase five wire system |
A、B、C、N、PE | Bus setting | Three phase four wire system Three phase five wire system |
Operation mode | Electromagnetic type Spring energy storage type |
Protection level | IP40 | Operation mode | Manual, Electric | Overall dimension (W×D×H) mm | 1100×1200×2300 (below 1000A) |